With S&A industrial chiller cw 5000, your CO2 glass laser tube can be perfectly cooled. Up to 120W DC laser tube, this small water chiller is capable of providing superior cooling. It features high control accuracy of ±0.3°C with cooling capacity up to 800W. Having a small footprint, CW5000 chiller takes up less floor space for CO2 laser engraving cutting machine users and it has multiple choices of water pumps and optional 220V or 110V powers. Designed with intelligent temperature control function, this portable water chiller unit can keep your CO2 laser tube at a water temperature you preset, automatically adjusting the temperature for you to avoid the occurrence of condensate water.
Model: CW-5000
Machine Size: 58 X 29 X 47cm (L X W X H)
Warranty: 2 years
Standard: CE, REACH and RoHS
Product Parameters
Model |
CW-5000TG |
CW-5000DG |
CW-5000TI |
CW-5000DI |
|
Voltage |
AC 1P 220-240V |
AC 1P 110V |
AC 1P 220-240V |
AC 1P 110V |
|
Frequency |
50/60Hz |
60Hz |
50/60 Hz |
60Hz |
|
Current |
0.4~3.1A |
0.4~5.3A |
0.8~3.5A |
0.8~5.7A |
|
Machine power |
0.44/0.46kW |
0.43kW |
0.51/0.53kW |
0.5kW |
|
Compressor power |
0.37/0.39kW |
0.38kW |
0.37/0.39kW |
0.38kW |
|
0.5/0.53HP |
0.51HP |
0.5/0.53HP |
0.51HP |
||
Nominal cooling capacity |
3037/3686Btu/h |
3514Btu/h |
3037/3686Btu/h |
3514Btu/h |
|
0.89/1.08kW |
1.03kW |
0.89/1.08kW |
1.03kW |
||
765/928Kcal/h |
885Kcal/h |
765/928Kcal/h |
885Kcal/h |
||
Refrigerant charge |
280g |
300g |
280g |
300g |
|
Pump power |
0.03kW |
0.1kW |
|||
Max. lift |
10M |
25M |
|||
Max. flow |
10L/min |
16L/min |
|||
N.W. |
21Kgs |
22Kgs |
25Kgs |
24Kgs |
|
G.W. |
24Kgs |
25Kgs |
28Kgs |
27Kgs |
|
Refrigerant |
R-134a |
||||
Precision |
±0.3℃ |
||||
Reducer |
Capillary |
||||
Tank capacity |
6L |
||||
Inlet and outlet |
OD 10mm barbed connector |
10mm fast connector |
|||
Dimension |
58 X 29 X 47cm (L X W X H) |
||||
Package dimension |
65 X 39 X 51cm (L X W X H) |
The working current can be different under different working conditions. The above information is for reference only. Please subject to the actual delivered product.
Product Features
* Cooling Capacity: 800W
* Active cooling
* Temperature stability: ±0.3°C
* Temperature control range: 5°C ~35°C
* Refrigerant: R-134a
* Compact, portable design and quiet operation
* High efficiency compressor
* Top mounted water fill port
* Integrated alarm functions
* Low maintenance and high reliability
* 50Hz/60Hz dual-frequency compatible available
* Optional dual water inlet & outlet
FAQ
Is S&A Chiller a trading company or a manufacturer?
We are professional industrial chiller manufacturer since 2002.
What is the recommended water used in the industrial water chiller?
The ideal water should be deionised water, distilled water or purified water.
How often should I change out the water?
Generally speaking, the water changing frequency is 3 months. It can also depend on the actual working environment of the recirculating water chillers. For example, if the working environment is too inferior, the changing frequency is suggested to be 1 month or shorter.
What is the ideal room temperature for the chiller?
The working environment of the industrial water chiller should be well ventilated and the room temperature should not be higher than 45 degree C.
How to prevent my chiller from freezing?
For users living in high latitude areas especially in winter, they often face the frozen water problem. To prevent the chiller from freezing, they can add an optional heater or add anti-freezer in the chiller.
Thanks for your order!
Questions, issues or concerns? I'd love to help you!